Installation Guide
Three Phase Inverter with Synergy Technology
Technical Specifications (North America)
Three Phase Inverters for the
277/480V Grid
Three Phase
Inverters for th
e
208V Grid
SE66.6KUS SE100KUS SE43.2KUS Units
OUTPUT
Rated AC power output 66600 100000 43200 VA
Maximum AC power
output
66600 100000 43200 VA
AC Output Line
Connections
4-wire WYE (l1-L2-L3) plus PE
4-wire WYE (l1-
L2-L3) plus PE or
3 wire Delta
AC output voltage
minimum-nominal
-
maximum (L-N)
(1)
244-277-305 105-120-132.5 Vac
AC output voltage
minimum-nominal
-
maximum (L-L)
1
AC frequency min-nom-
max
1
422.5-480-529 182-208-229 Vac
59.3-60-60.5 59.3-60-60.5 Hz
Max. continuous output
current (per Phase)@277
V
80 120 A
GFDI threshold 1 A
Utility monitoring,
islanding protection ,
Configurable Power
Factor, country
configurable Thresholds
Yes
INPUT
Maximum DC power
(Module STC)
90000 /45000 135000/45000 58200/19400 W
Transformer-less,
ungrounded
Yes
(1)
For other regional settings please contact SoalrEdge support
Three Phase Inverter with Synergy Technology - Technical Specifications
(North America) 103