StorEdge Specs

SolarEdge Single Phase StorEdge Inverter
for North America SE7600A-USS
SE7600A-USS
OUTPUT - AC (LOADS/GRID)
Rated AC Power Output 7600 VA
Max AC Power Output 8350 VA
AC Output Voltage Min-Nom-Max (L-L)
(1)
211-240-264 Vac
AC Frequency Min-Nom-Max
(1)
59.3 - 60 - 60.5 Hz
Maximum Connuous Output Current @240V 32 A
GFDI 1 A
Ulity Monitoring, Islanding Protecon, Country Congurable Thresholds Yes
Charge Baery from AC (if Allowed) Yes
THD <3 %
Power factor with rated power >0.99 (congurable; 0.9 leading to 0.9 lagging)
Typical Nighme Power Consumpon <5 W
OUTPUT - AC (BACKUP POWER)
(2)
Rated AC Power Output 5000
(3)
VA
Max AC Power Output - Surge 7600 for 10sec VA
AC Output Voltage Min-Nom-Max (L-L) 211-240-264 Vac
AC Output Voltage Min-Nom-Max (L-N) 105-120 -132 Vac
AC Frequency Min-Nom-Max 55 - 60 - 65 Hz
Maximum Connuous Output Current @240V - Backup Mode 21 A
Max Connuous Output Current per Phase @120V 25 A
GFDI 1 A
AC Circuit Breaker Yes
THD <5 %
Power factor with rated power 0.2 leading to 0.2 lagging
Automac switchover me <2 sec
Typical Nighme Power Consumpon <5 W
INPUT - DC (PV and BATTERY)
Transformer-less, Ungrounded Yes
Max Input Voltage 500 Vdc
Nom DC Input Voltage 400 Vdc
Reverse-Polarity Protecon Yes
Ground-Fault Isolaon Detecon 600kΩ Sensivity
Maximum Inverter Eciency 98 %
CEC Weighted Eciency 97. 5 %
INPUT - DC (PV)
Maximum DC Power (STC) 10250 W
Max Input Current
(4)
23 Adc
2-pole Disconnecon Yes
INPUT - DC (BATTERY)
Connuous Peak Power 3300 W
Number of Baeries per Inverter
(5)
Up to 2, for double capacity
Max Input Current 8.5 Adc
2-pole Disconnecon Yes
DC Fuses on Plus and Minus 12A (eld replaceable)
ADDITIONAL FEATURES
Supported Communicaon Interfaces RS485 for baery, RS485, Ethernet, ZigBee (oponal)
Baery Power Supply Yes, 12V / 53W
Revenue Grade Data, ANSI C12.1 Oponal
(6)
Integrated AC, DC and Communicaon Connecon Unit Yes
AC Disconnect Yes
Manual Inverter Bypass Switch Yes
DC Voltage Rapid Shutdown (PV and Baery) Yes, according to NEC 2014 690.12
Auto-transformer thermal protecon Yes
Single inverter for PV, grid-ed storage and backup power
Includes the hardware required to provide automac backup power to backed-up loads in case of grid interrupon
Includes all interfaces needed for baery connecon