Product Specifications

StorEdge
TM
Single Phase Inverter
for North America
SE3800A-US, SE7600A-US
SE3800A-US SE7600A-US
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, UL9540,CSA 22.2
Grid Connecon Standards IEEE1547, Rule 21, Rule 14H
Emissions FCC part15 class B
INSTALLATION SPECIFICATIONS
AC Output (Loads/Grid) conduit size / AWG range 1” / 14-6 AWG
AC Output (Backup) conduit size / AWG range 0.75-1” knockouts / 14-6 AWG
AC Input (Auto-transformer) conduit size / # of
Strings / AWG range
0.75-1” / 14-6 AWG
DC Input (PV) conduit size / AWG range 0.75” / 1-2 Strings 14-8 AWG
DC Input (Baery) conduit size / AWG range 0.75” / 12-10 AWG
Dimensions with Connecon Unit (HxWxD) 37 x 12.5 x 7.2 / 940 x 315 x 184 in / mm
Weight with Connecon Unit 58.5 / 26.5 lb / kg
Cooling Natural convecon and internal fan (user replaceable)
Noise <50 dBA
Min - Max Operang Temperature -13 to +140 / -25 to +60 ˚F / ˚C
Protecon Rang NEMA 3R
Inverter Interface