Product Specifications

StorEdge
TM
Single Phase Inverter
for North America
SE3800A-US
(1)
,
SE7600A-US
(1)
Single inverter for PV, grid-ed storage and backup power
Includes the hardware required to provide automac backup power to backed-up loads in case of grid interrupon
Includes all interfaces needed for baery connecon
UL1741 SA cered, for CPUC Rule 21 grid compliance
SE3800A-US SE7600A-US
OUTPUT - AC (LOADS/GRID)
Rated AC Power Output 3800 7600 VA
Max AC Power Output 4175 8350 VA
AC Output Voltage Min-Nom-Max (L-L)
(2)
211-240-264 Vac
AC Frequency Min-Nom-Max
(2)
59.3 - 60 - 60.5 Hz
Maximum Connuous Output Current @240V 16 32 A
GFDI 1 A
Ulity Monitoring, Islanding Protecon, Country Congurable
Thresholds
Yes
Charge Baery from AC (if Allowed) Yes
THD <3 %
Typical Nighme Power Consumpon <5 W
OUTPUT - AC (BACKUP POWER)
(3)
Rated AC Power Output 5000
(4)
VA
Max AC Power Output - Surge (for 10 seconds) 7000
(4)
VA
AC Output Voltage Min-Nom-Max (L-L) 211-240-264 Vac
AC Output Voltage Min-Nom-Max (L-N) 105-120 -132 Vac
AC Frequency Min-Nom-Max 55 - 60 - 65 Hz
Maximum Connuous Output Current @240V - Backup Mode 21 A
Max Connuous Output Current per Phase @120V 25 A
GFDI 1 A
AC Circuit Breaker Yes
THD <5 %
Automac switchover me <2 sec
INPUT - DC (PV and BATTERY)
Transformer-less, Ungrounded Yes
Max Input Voltage 500 Vdc
Nom DC Input Voltage 400 Vdc
Reverse-Polarity Protecon Yes
Ground-Fault Isolaton Detecon 600kΩ Sensitvity
Maximum Inverter Eciency 98 %
CEC Weighted Eciency 97. 5 %
INPUT - DC (PV)
Maximum DC Power (STC) 5100 10250 W
Max Input Current
(5)
13 23 Adc
2-pole Disconnecon Yes
INPUT - DC (BATTERY)
Supported Baery Types LG Chem RESU10H
Number of Baeries per Inverter 1 or 2
(6)
Connuous Power 5000 W
Peak Power 7000 W
Max Input Current 17.5 Adc
2-pole Disconnecon Yes
DC Fuses on Plus and Minus 25A (eld replaceable)
ADDITIONAL FEATURES
Supported Communicaon Interfaces RS485 for baery, RS485, Ethernet, Cellular, ZigBee (oponal)
Revenue Grade Data, ANSI C12.20 Oponal
(7)
Integrated AC, DC and Communicaon Connecon Unit Yes
AC Disconnect Yes
Manual Inverter Bypass Switch Yes
DC Voltage Rapid Shutdown (PV and Baery) Yes, according to NEC 2014 and 2017 690.12
(8)
Auto-transformer thermal protecon Yes
(1)
These specicaons apply to inverters with part numbers SExxxxA-USS2 and connecon unit model number BCU-1PH-USS
(2)
For other regional sengs please contact SolarEdge Support
(3)
Not designed for standalone applicaons and requires AC for commissioning
(4)
The rated AC power output is the minimum between the AC Power Output and the baery connuous peak power
(5)
A higher current source may be used; the inverter will limit its input current to the values stated
(6)
When connecng two LG Chem baeries, each baery must have a dierent part number; supporng SolarEdge rmware required
(7)
Revenue grade inverter P/N: SExxxxA-USS2xxxYx or SExxxxA-USS2xxxMx
(8)
In case the inverter is not located in an accessible locaon for emergency responders (according to NEC 2017), use inverters with P/N SExxxxA-USS2Rxxxx ; for more informaon refer to:
hps://www.solaredge.com/sites/default/les/storedge_backup_installaon_guide_NA.pdf