Installation Manual
Appendix D – Detailed System Connection
52
Table 6: Backup Power Only – Two Battery Configuration notes
Note
Description
Note 1
Recommended StorEdge inverter fuses in:
12A 600VDC Quick-Acting, 10 x 38 mm Solar Midget Fuses
(Example: Littelfuse P/N 0SPF012)
Note 2
External fused combiner box is needed to support two batteries
Note 3
Auto-transformer connection:
6ft max
Use 10 AWG wire for grounding
Note 4
Battery connection:
35ft max
Distance larger than 5ft requires installation of external DC safety
switch on the battery side
Control [B-,A+] must be twisted pair
Note 5
Use a twin-wire ferrules to daisy chain the thermal wiring
Note 6
GFDI in backed-up loads distribution panel:
Install the GFDI (Ground-Fault Detector Interrupter) in accordance with
applicable local standards and directives.