Installation Manual
Appendix D – Detailed System Connection
48
Table 5: Backup Power Only - Basic Configuration notes
Note
Description
Note 1
Recommended StorEdge inverter fusesn:
12A 600VDC Quick-Acting, 10 x 38 mm Solar Midget Fuses (Example:
Littelfuse P/N 0SPF012)
Note 2
Auto-transformer connection:
6ft max
Use 10 AWG wire for grounding
Note 3
Battery connection:
35ft max
Distance larger than 5ft requires installation of external DC safety
switch on the battery side
Control [B-,A+] must be twisted pair
Note 4
GFDI in backed-up loads distribution panel:
Install the GFDI (Ground-Fault Detector Interrupter) in accordance
with applicable local standards and directives.