Installation Manual

Backup Power Only - System Configurations
21
8 If ## 01 or Prot 01, the battery and/or meter are not configured or communicating correctly. Check the configuration.
Check the wiring connection. Proceed with step 10 below.
9 If ## = 01 and Prot = 01 the battery is configured and communicating properly. Skip steps 10 to 13 below and proceed with
set up backup power only as described below.
10 Select Communication RS485-1 Conf Device Type Multi-devices. A list of devices is displayed.
11 Configure Battery 1:
12 Select Battery 1. The battery configuration screen is displayed.
13 Configure the battery: Device Type Battery Pack
To set up Backup Power Only:
1 Enter Setup mode to display the main menu.
2 From the main menu, select Power Control. A menu similar to the following is displayed:
3 Select Energy Manager. The following screen is displayed:
4 Select Energy Ctrl.
5 Select Backup only. The Energy Manager screen changes to display the following:
Verifying Communication:
After connecting and configuring a communication option, perform the following steps to check that the connection to the
monitoring server has been successfully established.
1 Turn on the AC to the inverter by turning ON the circuit breaker on the main distribution panel.
2 Wait for the inverter to connect to the SolarEdge monitoring portal. This may take up to two minutes.
A status screen similar to the following appears on the LCD panel: