Installation Manual

Backup Power Only - System Configurations
20
Basic Configuration
This configuration is based on one of each of the StorEdge components, other than the SolarEdge Electricity Meter, and is
suitable for most residential systems.
Figure 16: Backup Power only - Basic configuration
To configure the system:
1 Terminate the battery connected on the RS485 bus:
2 Set the battery’s dip switches to ID 24: Move all dip switches to position 0 (to the right):
3 Make sure the wiring is connected according to the diagram above.
4 Upgrade the inverter firmware using the card supplied with the StorEdge Inverter. This will also configure the battery.
5 Configure Meter 2 to None:
Select Communication RS485-1 Conf Device Type Multi-devices.
Select Meter2 Meter Type None.
6 Check the Communication status screen and verify that the battery is properly connected and configured:
7 If Dev is not MLT, the system is not pre-configured and requires full configuration. Proceed with step 10 below.
<01> <01>