Installation Manual
Backup Power with Smart Energy Management - System Configurations
13
Additional Capacity with Two Batteries
For sites where additional battery capacity is needed (for example, to enable backed-up loads to be powered from the battery
for longer periods), two batteries may be connected to a single StorEdge inverter.
In this configuration, only one battery operates at any given time – i.e. the two batteries provide additional capacity only, not
additional power.
The DC connection of the two batteries to the StorEdge Inverter is done in parallel through an external fused combiner box (not
provided by SolarEdge), with a fuse rating of 12A/600V.
The control and thermal connection of the second battery is daisy chained to that of the first battery.
Figure 10: Backup Power with Smart Energy Management - Additional capacity with two batteries
► To configure the system:
For battery RS485 settings:
Battery 1 is not terminated with ID: 24 and
Battery 2 is terminated with ID: 25
1 Terminate the battery which is connected last on the RS485 bus (battery 2), and make sure the other battery (battery 1) is
not terminated:
Battery 1 - Unterminated battery:
Battery 2 - Terminated battery: