Figure 23: StorEdge Connection Unit fuses
Connecting the Strings to the Inverter
Figure 24: PVconnection
1. Verify that the AC circuit breaker is OFF.
2. Strip 5⁄16'' (8 mm) of the DC wire insulation.
3. Insert the DC conduit into the DC-side opening. Make sure the conduit is firmly
attached to the inverter enclosure and sealed properly.
4.
Connect the DC wires from the PV installation to the DC+ and DC- terminal blocks,
according to the labels on the terminals:
StorEdge Solution with Backup MAN-01-00262-1.5
58 Connecting the Strings to the Inverter