Installation Guide
Table Of Contents
- Disclaimers
- Revision History
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT INVERTER SAFETY INSTRUCTIONS
- Chapter 1: Overview
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Auto-transformer and Backed-up Loads Panel Installation (for Backup)
- Chapter 5: Meter Installation
- Chapter 6: Commissioning the Installation
- Chapter 7: StorEdge Inverter Connections
- Chapter 8: User Interface
- Chapter 9: Setting Up Communication to the Monitoring Platform
- Chapter 10: System Configuration
- Appendix A: Troubleshooting
- Appendix B: Opening Conduit Drill Guides
- Appendix C: Replacing and Adding System Components
- Appendix D: External Rapid Shutdown
- Appendix E: Mechanical Specifications
- Appendix F: Powering the LG Chem Battery Off and On
- StorEdge Single Phase Inverter with Connection Unit for High Power Technical ...

Appendix A: Troubleshooting
This appendix describes how to troubleshoot StorEdge-related errors.
Communication Troubleshooting
When a battery and a meter are connected (2 devices connected to the same bus), the
following should appear in the Communication status screen:
D e v P r o t # #
R S 4 8 5 - 1 < M L T > < 0 2 > < 0 2 >
Z i g B e e < - - - > < - - > < - - >
Device type, number and protocol are displayed incorrectly
If one or more of the following occurs, the meter(s) or the battery are not
communicating with the inverter:
If Dev is not MLT (Multi) , the system is not pre-configured and requires full
configuration. Configure the system as described in
Configuring the RS485 Bus for
Battery and Meter Connection
on page 111.
If ## < 02, the meter and/or the battery are not configured correctly. Check the
configuration.
If Prot < 02, the meter and/or the battery is not communicating correctly. Check
the configuration and wiring connection.
If Prot = ##– the battery and meter are configured and communicating properly.
Troubleshooting Ethernet Communication
When using Ethernet communication, use the Server Communication Status window
to identify the location of the error:
S e r v e r : L A N < S _ O K >
S t a t u s : < O K >
x x x x x x x x
< E R R O R M E S S A G E >
xxxxxxxx is a string of 1s and 0s showing an eight-bit communication connection
status. 1 indicates OK and 0 indicates an error.
Bit
Location
Error Message Cause and Troubleshooting
1st LAN Disconnected
Physical connection fault. Check the
cable pin-out assignment and cable
connection. Refer to
Creating an
Appendix A: Troubleshooting 123
StorEdge Solution with Backup MAN-01-00262-1.5