SE9kUS Specs
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE
are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein
are trademarks of their respective owners. Date: 06/2015. V.01. Subject to change without notice.
Three Phase Inverters for the 208V Grid for North America
SE9KUS / SE14.4KUS
(1)
SE9KUS SE14.4KUS
OUTPUT
RatedACPowerOutput 9000 14400 VA
MaximumACPowerOutput 9000 14400 VA
ACOutputLineConnecons 4-wireWYE(L1-L2-L3-N)plusPEor3wireDelta
ACOutputVoltageMinimum-Nominal-
Maximum
(2)
(L-N)
105-120-132.5 Vac
ACOutputVoltageMinimum-Nominal-
Maximum
(2)
(L-L)
183-208-229 Vac
ACFrequencyMin-Nom-Max
(2)
59.3-60-60.5 Hz
Max.ConnuousOutputCurrent(perPhase) 25 40 A
GFDI Threshold 1 A
UlityMonitoring,IslandingProtecon,
C o u n t r y C o n g u r a b l e S e t P o i n t s
Yes
INPUT
MaximumDCPower(ModuleSTC) 12150 19400 W
Transformer-less, Ungrounded Yes
MaximumInputVoltageDCtoGnd 250 300 Vdc
MaximumInputVoltageDC+toDC- 500 600 Vdc
NominalInputVoltageDCtoGnd 200 Vdc
NominalInputVoltageDC+toDC- 400 Vdc
MaximumInputCurrent 26.5 38 Adc
Max.InputShortCircuitCurrent 45 Adc
Reverse-PolarityProtecon Yes
Ground-FaultIsolaonDetecon 1MΩSensivity
CECWeightedEciency 96.5 97 %
Night-mePowerConsumpon <3 <4 W
ADDITIONAL FEATURES
SupportedCommunicaonInterfaces RS485,Ethernet,ZigBee(oponal)
RapidShutdown–NEC2014690.12 Withinstallaonofrapidshutdownkit
(3)
STANDARD COMPLIANCE
Safety UL1741,UL1699B,UL1998,CSA22.2
GridConneconStandards IEEE1547
Emissions FCCpart15classB
INSTALLATION SPECIFICATIONS
ACoutputconduitsize/AWGrange 3/4”minimum/12-6AWG
DCinputconduitsize/AWGrange 3/4”minimum/12-6AWG
NumberofDCinputs 2pairs 3pairs(withfusesonplus&minus)
(4)
Dimensions(HxWxD) 21x12.5x10.5/540x315x260 in/mm
DimensionswithSafetySwitch(HxWxD) 30.5x12.5x10.5/775x315x260 in/mm
Weight 73.2/33.2 99.5/45
WeightwithSafetySwitch 79.7/36.2 106/48
Cooling Fans(userreplaceable)
Noise <50 <55 dBA
OperangTemperatureRange -40to+140/-40to+60 ˚F/˚C
ProteconRang NEMA3R
(1)
For277/480Vinvertersreferto:hp://www.solaredge.com/les/pdfs/products/inverters/se-three-phase-us-inverter-datasheet.pdf
(2)
ForotherregionalsengspleasecontactSolarEdgesupport.
(3)
RapidshutdownkitP/N:contactSolarEdge.
(4)
Fieldreplacementkitfor1pairofinputsP/N:DCD-3PH-1TBK.