Install Manual

Table Of Contents
o
Wheninstallinginvertersoneabovetheother,leaveatleast8"(20cm)betweenthetopofan
inverterandthebottomoftheSafetySwitch.
o
Wheninstallinginverterssidebyside,followtheseclearancespecifications:
Location Indoor Installation Outdoor Installation
Locations where the annual
average high temperature
1
is
below 25˚C / 77˚F
20 cm / 8"
between inverters
5 cm / 2" between inverters (if
inverters are also installed one above
the other, maintain the indoor
installation clearance)
Locations where the annual
average high temperature
1
is
above 25˚C / 77˚F
40 cm / 16"
between inverters
Figure 16: Clearance
3. Positionthemountingbracketagainstthewall/poleandmarkthedrillingholelocations(referto
MechanicalSpecificationsonpage65forinverterandmountingbracketdimensions):
o
Ensurethattheflatedgeofthebracketisatthebottom,asinFigure17.
o
Useatleasttwobracketholes.Additionalholescanbeusedtofixthebracket.Determinewhich
andhowmanyholestouseaccordingtomountingsurfacetypeandmaterial.
4. Drilltheholesandmountthebracket.Verifythatthebracketisfirmlyattachedtothemounting
surface.
1
Annual average high temperature the average of the 12 monthly average highs, for example:
Refer to http://www.weatherbase.com/ to find the value in your location.
-Three Phase System Installation Guide MAN-01-00527-1.1
30
Mounting the Inverter