NOTE
The symbol appears at grounding points on the SolarEdge equipment. This symbol is also used in
this manual.
NOTE
ASolarEdgeinvertermaybeinstalledinasitewithagenerator,howevermustnotoperateat
thesametimeasthegenerator.
Operatinganinverterandageneratorsimultaneouslywillvoidthewarranty.SolarEdgerequires
installingaphysicalorelectronicinterlock,whichwillpreventthegeneratorandinverterfrom
operatingsimultaneously.Interlockprocurement,installation,maintenanceandsupportare
theresponsibilityoftheinstaller.Damagetotheinverterduetoincorrectinterlockinstallation
oruseofaninterlockthatisincompatiblewiththeSolarEdgesystemwillrendertheSolarEdge
warrantyinvalid.
IMPORTANT SAFETY INFORMATION
l Building or structures with both utility service and a PV system, complying with NEC 690.12, shall
have a permanent plaque or directory including the following wording:PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID SHUTDOWN. The term “PHOTOVOLTAIC” may be replaced with
“PV.” The plaque or directory shall be reflective, with all letters capitalized and having a minimum
height of 9.5mm (3/8 in.) in white on red background.
l Attention -The system status indicator shall be installed in a location in close proximity to the
system actuator, where the indication of safe shutdown can be clearly seen.
l This rapid shutdown system is required to be provided with an actuating device or a status
indicator which shall be installed in a location accessible to first responders, or be connected to an
automatic system which initiates rapid shutdown upon the activation of a system disconnect or
activation of another type of emergency system.
l Additionally, in a prominent location near the actuator device the end use installation shall be
provided with a permanent marking including the following wording:PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID SHUTDOWN. The term “PHOTOVOLTAIC” may be replaced with
“PV”. The plaque or directory shall be reflective, with all letters capitalized and having a minimum
height of 9.5mm (3/8 in.) in white on red background.
-Three Phase System Installation Guide MAN-01-00527-1.1
10
IMPORTANTSAFETYINSTRUCTIONS