SE9K SetApp Enabled Manual
SE9KUS SE10KUS SE14.4KUS SE20KUS SE30KUS SE33.3KUS Units
ADDITIONAL FEATURES
Supported communication
interfaces
2 x RS485, Ethernet, Built-in GSM (Optional)
Inverter Commissioning With the SetApp mobile application using built-in Wi-Fi station for local connection
Rapid Shutdown – NEC 2014 and
2017 690.12
Automatic Rapid Shutdown upon ACgrid disconnect
(1)
RS485 Surge Protection Supplied with the inverter
Smart Energy Management Export Limitation
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA 22.2, Canadian AFCIaccording to T.I.L. M-07
Grid connection standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class B
RoHS Yes
INSTALLATION SPECIFICATIONS
AC output conduit size / AWG
range
3/4”
minimum /
12-6 AWG
3/4”
minimum /
12-6 AWG
3/4”
minimum /
8-4 AWG
3/4”
minimum /
12-6 AWG
3/4”
minimum /
8-4 AWG
3/4”
minimum /
8-4 AWG
DC input conduit size / # of
inputs/ AWG range
3/4” minimum / 12-6 AWG
Number of DC inputs 2 pairs
3 pairs (with
fuses on plus
& minus)
(2)
2 pairs
3 pairs(with
fuses on plus
& minus)
1
3 pairs(with
fuses on plus
& minus)
1
Dimensions (HxWxD) 21 x 12.5 x 10.5 / 540 x 315 x 260 in/mm
Dimensions with Safety Switch
(HxWxD)
30.5 x 12.5 x 10.5 / 775 x 315 x 260 in/mm
Weight 73.2 / 33.2 73.2 / 33.2 99.5 / 45 73.2 / 33.2 99.5 / 45 99.5 / 45 lb/kg
Weight with Safety Switch 79.7 / 36.2 79.7 / 36.2 106 / 48 79.7 / 36.2 106 / 48 106 / 48 lb/kg
Cooling Fans (user replaceable)
Noise (typical) < 50 < 55 < 50 < 55 < 55 dBA
Operating temperature range
(3)
-40 to +140 / -40 to +60 ºF/ºC
Operating humidity – non
condensing
< 95 %
Protection rating NEMA3R
FAULTCURRENTCONTRIBUTION
Inom 25 12 40 24 36.5 40 A
Peak 59 40 70 59 147 92 A
1 cycle RMS
(4)
20 10 25 14 14 38.1 A
3 cycle RMS
(5)
12 10 16.5 8 8.5 39 A
Duration
(6)
15 49 18 9 5 150 ms
(1)
P/N SE9K-US0xxxxxx has Manual Rapid Shutdown for NEC2014 compliance (NEC 2017 compliance with outdoor installation)
(2)
Field replacement kit for 1 pair of inputs P/N: DCD-3PH-1TBK. Field replacement kit for 3 pairs of fuses and holders P/N: DCD-6PHK-S1.
(3)
SolarEdge’s 9kW and 20kW inverters operate at full power and full currents up to a temperature of 122°F / 50°C. The inverters may be used above this temperature with reduced
ratings. For more information, refer to http://www.solaredge.com/files/pdfs/se-temperature-derating-note-na.pdf.
(4)
1 cycle RMS – the integral on one cycle (60Hz) duration
(5)
3 cycle RMS – the integral on 3-cycle duration
(6)
Duration - time by which fault current reaches 0
Technical Specifications - Three Phase Inverters (North America) 98
MAN-01-00527-1.
2
Technical
Specifications
-
Three
Phase
Inverters
(North
America)