Installation Guide
If using a cable longer than 10 m/33 ft in areas where there is a
risk of induced voltage surges by lightning, it is recommend to
use external surge protection devices. For details refer to:
https://www.solaredge.com/sites/default/files/overvoltage_surge_
protection_na.pdf.
If grounded metal conduit are used for routing the communication wires, a
lightning protection device is not required.
If not using surge protection, connect the grounding wire to the first inverter
in the RS485 chain; make sure the grounding wire is not in contact with other
wires. Connect the grounding wire to the grounding bus-bar in the
Connection Unit.
NOTE
An additional RS485 port (RS485-Plug-in) is available from
SolarEdge, allowing the creation of RS485 Bus Connection;
Refer to
To connect to the monitoring platform:
1. Designate a single inverter as the connection point between the RS485 bus and the
SolarEdge monitoring platform. This inverter will serve as the master inverter.
2. Connect the master to the SolarEdge monitoring platform via the LAN or ZigBee or
cellular communication option.
3. Install an RS485 Plug-in in every EV Charging single phase inverter , refer to the
'Installing the RS485 Expansion Module' chapter in the RS485 Expansion Kit Installation
Guide and to configure the RS485 bus refer to the following sections.
EV Charging Single Phase Inverter Guide MAN-01-00404-1.2
78 Creating an RS485 Bus Connection