Installation Guide

Connecting the AC Grid to the Connection Unit
1. Strip 5/16'' (8mm) of the AC wire insulation.
2. Insert the AC conduit into the AC-side drill guide that was opened.
NOTE
Connect the equipment grounding before connecting the AC wires to the AC
terminal block.
Veillez à relier le conducteur de PE (la terre) avant de connecter les fils CA au
bornier CA.
3. Connect the wires to the appropriate terminal blocks according to the labels on the
terminal blocks (N, , L1 and L2).
4.
Use a standard flat-blade screwdriver to connect the wires to the spring-clamp
terminals. The screwdriver blade should fit freely in the terminal opening. Too large
a blade can crack the plastic housing.
a. Insert the screwdriver and press the release mechanism and open the clamp.
b.
Insert the wire into the round opening and remove the screwdriver – the wire is
automatically clamped.