Installation Guide

SE3800H-US SE7600H-US Unit
Operating Temperature
Range
(1)
,
(2)
-13 to +140 / -25 to +60 (-40°F / -40° C option) °F/ °C
Protection Rating NEMA 4X(Inverter with Safety Switch)
Recommended OCPD size per grid:
CAUTION!
To reduce the risk of fire, connect only to a circuit provided with 50 amperes
maximum branch circuit overcurrent protection in accordance with the
product's listing and local and national codes: ANSI/NFPA 70 National
Electrical Code and CSA C22.1–15 Canadian Electrical Code, Part 1.
ATTENTION!
Pour duire le risqué d’incendie, raccorder uniquement à un circuit dote d’un
dispositif de protection contre les surintensités de la rivation d’au plus 50
amres, conforment à la liste des produits et aux codes locaux et
nationaux:ANSI/NFPA 70 National Electrical Code et CSA C22.1–15 Canadian
Electrical Code, Part 1.
Inverter
Maximum Output
Current (A)
Minimum Fuse
Rating (A)
Maximum Fuse
Rating (A)
SE3800H-US 16 20 50
SE5000H-US 21
30
50
SE6000H-US
25 35
50
SE7600H-US 32 40 50
Default Trip Limits and Times According to IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-
points, and can be aggregated above 30kW on a single Point of Common
Connection. The default settings are in compliance with IEEE1547. Utility
authorization is required to change these set-points.
Voltage Range (% of Base Voltage) Maximum Clearing Time (Sec)
V < 50% 0.16
50 % < V < 88% 2.00
(1)
Power de-rating from 50° C.
(2)
-40 version P/N: SExxxxH-US000xxV4 (W4 for revenue grade inverter).
EV Charging Single Phase Inverter Guide MAN-01-00404-1.2
102Default Trip Limits and Times According to IEEE1547