Installation Guide

SE3800H-US SE7600H-US Unit
Max. Input Short Circuit
Current
45 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation
Detection
600 kΩ Sensitivity
Maximum Inverter
Efficiency
99.2 %
CEC Weighted Efficiency 99 %
Nighttime Power
Consumption
< 2.5 W
ADDITIONAL FEATURES
Supported Communication
Interfaces
RS485, Ethernet, ZigBee (optional), Cellular
(Optional)
Revenue Grade Data, ANSI
C12.20
Optional
(1)
Rapid Shutdown - NEC
2014 and 2017 690.12
Automatic Rapid Shutdown upon AC grid
disconnect
STANDARD COMPLIANCE
Safety
UL1741, UL1741 SA, UL1699B, CSA C22.2,
Canadian AFCI according to T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule14 (HI)
Emissions FCC part15 class B
RoHS Yes
INSTALLATION SPECIFICATIONS
AC output conduit size /
AWG range
Minimum 0.75 conduit /14-6 AWG
DC input conduit size / # of
strings / AWG range
Minimum 0.75 conduit / 1-2 strings / 14-6
AWG
Dimensions with Safety
Switch (HxWxD)
17.7 x 14.6 x 6.8 / 450 x 370 x 174 in/mm
Weight with Safety Switch 22 / 10 lb / kg
Noise < 25 dBA
Cooling Natural Convection
Natural convection
and internal fan (user
replaceable)
(1)
Revenue grade inverter P/N: SExxxxH-US000xxW2.
Technical Specifications - EV Charging Single Phase Inverter (North America)
101