SE3000H-US-SE11400H-US Single Phase Inverter with HD-Wave Technology - North America
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US
OUTPUT
Rated AC Power Output 3000
3800 @ 240V
3300 @ 208V
5000
6000 @ 240V
5000 @ 208V
7600 10000
11400 @ 240V
10000 @ 208V
VA
Maximum AC Power Output 3000
3800 @ 240V
3300 @ 208V
5000
6000 @ 240V
5000 @ 208V
7600 10000
11400 @ 240V
10000 @ 208V
VA
AC Output Voltage Min.-Nom.-Max.
(211 - 240 - 264)
Vac
AC Output Voltage Min.-Nom.-Max.
(183 - 208 - 229)
-
-
- -
Vac
AC Frequency (Nominal) 59.3 - 60 - 60.5
(1)
Hz
Maximum Continuous Output
Current @240V
12.5 16 21 25 32 42 47.5 A
Maximum Continuous Output
Current @208V
- 16 - 24 - - 48.5 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection,
Country Congurable Thresholds
Ye s
INPUT
Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 W
Maximum DC Power @208V - 5100 - 7750 - - 15500 W
Transformer-less, Ungrounded Ye s
Maximum Input Voltage 480 Vdc
Nominal DC Input Voltage 380 400 Vdc
Maximum Input Current @240V
(2)
8.5 10.5 13.5 16.5 20 27 30.5 Adc
Maximum Input Current @208V
(2)
- 9 - 13.5 - - 27 Adc
Max. Input Short Circuit Current 45 Adc
Reverse-Polarity Protection Ye s
Ground-Fault Isolation Detection 600k
Sensitivity
Maximum Inverter Eciency 99 99.2 %
CEC Weighted Eciency 99
99 @ 240V
98.5 @ 208V
%
Nighttime Power Consumption < 2.5 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional)
Revenue Grade Data, ANSI C12.20 Optional
(3)
Rapid Shutdown - NEC 2014 and
2017 690.12
Automatic Rapid Shutdown upon AC Grid Disconnect
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC Part 15 Class B
INSTALLATION SPECIFICATIONS
AC Output Conduit Size / AWG Range 1" Maximum / 14-6 AWG 1" Maximum /14-4 AWG
DC Input Conduit Size / # of Strings /
AWG Range
1" Maximum / 1-2 rings / 14-6 AWG 1" Maximum / 1-3 rings / 14-6 AWG
Dimensions with Safety Switch
(HxWxD)
17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185
in /
mm
Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 lb / kg
Noise < 25 <50 dBA
Cooling Natural Convection
Operating Temperature Range -13 to +140 / -25 to +60
(4)
(-40˚F / -40˚C option)
(5)
˚F / ˚C
Protection Rating NEMA 4X (Inverter with Safety Switch)
(1)
For other regional settings please contact SolarEdge support
(2)
A higher current source may be used; the inverter will limit its input current to the values ated
(3)
Revenue grade inverter P/N: SExxxxH-US000NNC2
(4)
For power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf
(5)
-40 version P/N: SExxxxH-US000NNU4
Single Phase Inverter
with HD-Wave Technology for North America
SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/
SE7600H-US / SE10000H-US / SE11400H-US
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All
other trademarks mentioned herein are trademarks of their respective owners. Date: 03/2019/V01/ENG NAM. Subject to change without notice.