An error message is displayed
IfError 185 Meter Comm. Errorisdisplayedinthemeterstatusscreen,verifyproperconnectionof:
l TheRS485cablesandconnectors
l TheACconnectionofthemeter
Total [Wh] Import value is not advancing
Iftheinverterisnotproducingpower,andthereispowerconsumptionbytheloads,theTotal[Wh]
valueshouldbechanging.
IftheTotal[Wh]valueoftheImportmeterdisplaysasteadyvaluealthoughthesiteisconsumingpower,
checkthefollowing:
l ThemeterstatusLEDsarelit.IftheLEDsareallOFF,themeterisnotconnectedtoapowersource.
o
CheckthemeterACconnection(10-pinterminalblock)
o
CheckthatthemeterbreakerisON
l Therearenolooseconnectionsatthe10-pinACwiringofthemeter.
l TheCTblackandwhitecablesarecorrectlyconnectedtothe6-pinconnectoronthemeter:
o
WhiteCTwireisconnectedtoL1white
o
BlackCTwireisconnectedtoL1black
l CTdirectionistowardsthegridandthegreenpowerLEDsareON.IftheLEDsarenotgreenindicating
importpower-theCTsarereversed.
Figure 40: Meter with CT
Appendix A: Troubleshooting
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
81