Installation Manual
Table Of Contents
- Disclaimers
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- Chapter 1: Overview
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Auto-transformer and Backed-up Loads Panel Installation (for Backup Only)
- Chapter 5: Electricity Meter Installation
- Chapter 6: StorEdge Inverter Connections
- Chapter 7: User Interface
- Chapter 8: Commissioning the Installation
- Chapter 9: System Configuration
- Chapter 10: Setting Up Communication to the Monitoring Portal
- Appendix A: Troubleshooting
- Appendix B: Replacing and Adding System Components
8.
SelectBattery Infoandcheckthebatteryinformation:
S N : < s e r i a l # >
M o d e l : < X X X X X X >
R a t e d P W R [ k W H ] : N / A
F W V e r . < X X X X X >
To verify the connection:
1.
PresstheinverterexternalLCDlightbuttontodisplaythestatusscreensoneaftertheother:
a. ChecktheRS485communicationstatus:
w w w w w w w w D e v P r o t # #
R S 4 8 5 - 1 < M L T > < 0 2 > < 0 2 >
l ThenumberunderProt(protocol)shoulddisplaythenumberofconfigureddevices.
l Thenumberunder##shoulddisplaythenumberofcommunicatingdevices.
Theabovescreenshowsanexampleof2devicesonthesamebus(e.g.meterandbattery).If
RGMispre-installed,andabatteryandanexternalmeterarealsoinstalled,thescreenshould
show<3><3>.
IfthenumberofdevicesunderProtdoesnotmatchthenumberunder##,referto
Troubleshootingonpage79
b. Checkthemeter(s):Inthemeter(s)statusscreencheckthatthestatusisOK.Thefollowingisan
exampleofthestatusofanExport(orExport+Import)meter:
E x p o r t M e t e r
S t a t u s : < O K >
< E r r o r M e s s a g e >
T o t a l [ W h ] : X X X X X X X
IfComm. Errorappears,refertoTroubleshootingonpage79.
c. Checkthebatteryinformation:identification,chargingstatusandpower,andtheoperating
mode.
B S N : X X X X X X X X X I D : 2 4
S O E : 8 9 % W W W W W P W R : 0 W
T o t a l : 0 W h
S t a t e : I d l e
IfComm. Errorappears,refertoTroubleshootingonpage79.
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
64
Configuring the RS485 Bus for Battery and Meter Connection