Configuration Menu Options
Country and Grid
Configuringthecountryandgridisavailableusingtheinternaluserbuttonsonly.
1.
SelecttheCountry optiontospecifythecountryinwhichtheinverterisinstalledandthegridto
whichitisconnected.Thisparametermayarrivepre-configured.Ifso,verifythatitissettothe
propercountry.
WARNING!
The inverter must be configured to the proper country in order to ensure that it complies with the
country grid code and functions properly with that country grids.
L'onduleur doit être configuré pour le pays approprié afin d'assurer un fonctionnement
convenable avec le réseau de ce pays.
Alistofcountriesisdisplayed.Ifnocountryisconfigured,thevalueis<NONE>.
NOTE
If an inverter is not configured to any country, it will not produce energy, and the following
message will be displayed on the LCD:
No Country Selected
Aplussign(+)nearthecountryindicatesthatanothermenuwillbedisplayedafterselection.
l WhenselectingAuto,theinverterautomaticallydetectstheusedgrid.
l WhenselectinganoptionwithNo NeutralorNo N,connectiontoNeutrallineisnotrequired.
Foranyotheroption,youmustconnecttheNeutralline.
2. Confirmyourcountryselectionintheconfirmationscreen:ToggletoYES andpressEnter.
Language
1. SelecttheLanguage optiontosetthelanguageinwhichtheLCDshoulddisplay.
2. Confirmyourlanguageselectionintheconfirmationscreen:ToggletoYESandpressEnter.
Communication
1.
SelecttheCommunication optiontodefineandconfigure:
l ThecommunicationoptionusedbytheinvertertocommunicatewiththeSolarEdge
monitoringportal
l ThecommunicationoptionusedtocommunicatebetweenmultipleSolarEdgedevicesor
otherexternalnon-SolarEdgedevices,suchaselectricitymetersorloggers.
2. SelectServer tosetwhichcommunicationmethodisusedtocommunicatebetweendevicesandthe
SolarEdgemonitoringportal.Refertoforafulldescriptionofthesecommunicationoptions.
NOTE
The Server menu shows only the communication options installed in the inverter.
ThefollowingshowsahierarchicaltreeofthemenuoptionsintheCommunication menu.
Fordetailedinformationaboutalltheconfigurationoptions,refertotheCommunicationOptions
ApplicationNote,availableontheSolarEdgewebsiteathttp://www.solaredge.us/files/pdfs/solaredge-
communication_options_application_note_v2_250_and_above.pdf.
Chapter 7: User Interface
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
45