DIPSwitch Setup according to System Application
VerifythattheDIPswitchesontheStorEdgeConnectionUnitaresetasdescribedinthefollowingtable,
accordingtothecomponentsusedinthesystem:
System components
Left DIP switch
(SW1) setup
Right DIP switch
(SW2) setup
Auto-transformer with connected over-temperature sensor Up (ON) - default Down (OFF) - default
No auto-transformer, or auto-transformer with over-
temperature sensor not connected
Up (ON) - default Up (ON)
Figure 25: StorEdge Connection Unit DIP switches
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0