Energy Hub with Prism Technology Installation Guide
Table Of Contents
- Disclaimers
- Revision History
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Overview
- Chapter 2: Installing the Power Optimizer
- Chapter 3: Installing the Inverter
- Chapter 4: Installing the Battery
- Chapter 5: Connecting the Inverter
- Chapter 6: Activating, Commissioning and Configuring the System
- Chapter 7: Setting Up Communication to the Monitoring Platform
- Appendix A: Errors and Troubleshooting
- Appendix B: Mechanical Specifications
- Appendix C: Replacing and Adding System Components
- Appendix D: Powering the LG Chem Battery Off and On
- Single Phase Energy Hub Inverter with Prism Technology - Technical Specificat...
- Support Contact Information
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US UNITS
Battery Storage
With Backup Interface for service up to 200A; Up to 3 inverters, 15kW
backup power, and 60kWh backup capacity
EVCharging Direct connection to Smart EV charger
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Wifi (optional), Cellular
Revenue Grade Metering, ANSI C12.20
Built - in
(3)
Integrated AC, DC and Communication
Connection unit
Yes
Inverter Commissioning
with the SetApp mobile application using built-in Wi-Fi Access Point for
local connection
DC Voltage Rapid Shutdown (PV and Battery) Yes, according to NEC 2014 and 2017 690.12
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, UL9540, CSA 22.2
Grid Connection Standards IEEE1547, Rule 21, Rule 14H
Emissions FCC part15 class B
INSTALLATION SPECIFICATIONS
AC Output Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
EV AC Output Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
DC Input (PV) Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
DC Input (Battery) Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
Dimensions with Connection Unit (HxWxD) 17.7 X 14.6 X 6.8 / 450 X 370 X 174
in/mm
Weight with Connection Unit 26 / 11.8 29.1 / 3.2 30.2 / 13.7 lb/kg
SolarEdge-Single Phase Energy Hub Inverter with Prism Technology MAN-01-00671-1.3
76