Recommended OCPD Size per Grid
Inverter Maximum Output Current (A) Minimum Fuse Rating (A) Maximum Fuse Rating (A)
SE3000H-US 12.5 20 50
SE3800H-US 16 20 50
SE5000H-US
24 @ 208V
21 @ 240V
30 50
SE6000H-US
24 @ 208V
25 @ 240V
30 @ 208V
35 @ 240V
50
SE7600H-US 32 40 50
SE10000H-US 42 60 80
SE11400H-US
48.5 @ 208V
47.5 @ 240V
70 @ 208V
60 @ 240V
80