SE6000HD-US Installation Manual
Table Of Contents
- Disclaimers
- Revision History
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Activating, Commissioning and Configuring the System
- Chapter 6: Setting Up Communication to the Monitoring Platform
- Appendix A: Errors and Troubleshooting
- Appendix B: Mechanical Specifications
- Appendix C: Replacing and Adding System Components
- Technical Specifications - Single Phase Inverters with HD-Wave Technology (No...
- Support Contact Information
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US
SE10000H-
US
SE11400H-US Unit
Nighttime Power
Consumption
< 2.5 W
ADDITIONAL FEATURES
Supported
Communication Interfaces
RS485, Ethernet, ZigBee (optional), Cellular (Optional)
Revenue Grade Data, ANSI
C12.20
Optional
(1)
Inverter Commissioning with the SetApp mobile application using built-in Wi-Fi access point for local connection
Rapid Shutdown - NEC
2014 and 2017 690.12
Automatic Rapid Shutdown upon AC Grid Disconnect
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule14 (HI)
Emissions FCC part15 class A
RoHS Yes
INSTALLATION SPECIFICATIONS
AC output conduit size /
AWG range
1” minimum / 14 - 6 AWG 1” minimum / 14-4 AWG
DC input conduit size / #
of strings / AWG range
1” minimum / 1-2 strings / 14-6 AWG
1” minimum / 1-3 strings /
14-6 AWG
Dimensions with Safety
Switch (HxWxD)
17.7 x 14.6 x 6.8 / 450 x 370 x 174
21.3 x 14.6 x 7.3 / 540 x 370
x 185
in/mm
(1)
Inverter with Revenue grade meter P/N: SExxxxH-US000BNC4; Inverter with Revenue grade and Export/Import meter P/N: SExxxxH-US000BNI4