3. Remove the plastic seal from one of the large openings.
4. Remove the rubber fitting from the gland and insert the CAT6 cable through the
gland and through the gland opening in the inverter.
5. Insert the cable through the opening in the Safety Switch towards the
communication board.
6.
Push the cable into the cut opening of the rubber fitting.
Figure 25: Communication gland and rubber fitting
CAT6 standard cables have eight wires (four twisted pairs), as shown in the diagram
below. Wire colors may differ from one cable to another. You can use either wiring
standard, as long as both sides of the cable have the same pin-out and color-coding.
RJ45 Pin #
Wire Color
(1)
10Base-T Signal
100Base-TX Signal
T568B T568A
1 White/Orange White/Green Transmit+
2 Orange Green Transmit-
3 White/Green White/Orange Receive+
4 Blue Blue Reserved
5 White/Blue White/Blue Reserved
6 Green Orange Received-
(1)
The inverterconnection doesnot support RX/TX polarity change. Supporting crossoverEthernetcables
depends on the switch capabilities.
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00541-1.4
54 Creating an Ethernet (LAN) Connection