Recommended OCPD size per grid:
Technical Specifications - Single Phase Inverters with HD-Wave Technology (North America)
Single Phase Inverter with HD-Wave Technology Specifications (North America) MAN-01-00308-1.3
81
Default Trip Limits and Times According to IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on a single Point of Common Connection.
The default settings are in compliance with IEEE1547. Utility authorization is required to change these set-points.
Voltage Range (% of Base Voltage) Max. Clearing Time (Sec)
0.16
2.00
1.00
0.16
V < 50%
50 % < V < 88%
110% < V < 120%
V > 120 %
Frequency Range (Hz) Max. Clearing Time (Sec)
0.16> 60.5
< 59.3 (Hawaii – 57) 0.16
Inverter Maximum Output Current (A) Minimum Fuse Rating (A) Maximum Fuse Rating (A)
208 VAC 240 VAC
SE3000H-US 12.5 20 --- 50
SE3800H-US 16 20 50 50
SE5000H-US 21 30 50 50
SE6000H-US 25 35 --- 50
SE7600H-US 32 40 --- 50
SE10000H-US 42 60 --- 80
SE11400H-US 47.5 60 --- 80