Installation Guide

Code
Error
Message
Troubleshooting
CPU
v3.18xx
and
below
CPU v3.19xx
and above
o
Iftheinverterislocatedfarfromthe
connectionpointtothegrid,usealarger
gaugeACwire.
o
Consultthegridoperator.
o
Ifpermittedbylocalauthorities,change
thegridprotectionvalues.Referto
http://www.solaredge.com/files/pdfs/vie
wing_grid_protection_values.pdf
56 18x38 V-LineMin
ACvoltagetoolow
o
Verifythattheinverterissettothecorrectcountry.
o
Consultthegridoperator.
o
Ifpermittedbylocalauthorities,changethegridprotection
values.Referto
http://www.solaredge.com/files/pdfs/viewing_grid_
protection_values.pdf
57,59,60 18x39/3B/3C
I-ACDC
L1/L2/L3
ACovercurrent.ContactSolarEdgesupport.
61 18x3D I-RCDSTEP
GroundCurrent–RCD.ContactSolarEdgesupport.
62 18x3E I-RCDMAX
64-66 18x40-59/A-F
F-L1/L2/L3
Max1/2/3
ACfrequencytoohigh(Line1/2/3)
o
Verifythattheinverterissettothecorrectcountry.
o
Consultthegridoperator.
o
Ifpermittedbylocalauthorities,changethegridprotection
values.Referto
http://www.solaredge.com/files/pdfs/viewing_grid_
protection_values.pdf
67-69 18x40-59/A-F
F-L1/L2/L3
Min1/2/3
ACfrequencytoolow(Line1/2/3)
Handleasfortheerrorabove.
96,98 18x60/18x62
Islanding
Trip1/2
ACgridvoltagemalfunction.WhenACvoltagereturnsthe
invertershouldrestartafterthereconnectiontime.
Iftheproblempersists,consultwiththegridoperator.
100-102 18x64-66 TZL1/L2/L3 ACovercurrent.ContactSolarEdgesupport.
111-113 18x6F/70/71
VsrgL1/L2/L3
Max
ACvoltagesurge.
o
ChecktheACconnectiontoinverter.
o
Verifythattheinverterissettothecorrectcountry.
o
Checkwiththegridoperatorifalargesurgesourceor
irregularloadexistsnearthesite.
o
Verifythattheoutputwiresizematches
thedistancebetweentheinverterand
thelocationofthegridconnection.
o
UsealargergaugewirefortheAC
Appendix A: Errors and Troubleshooting
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1