Product Specifications
SE43.2KUS
OUTPUT
Rated AC Power Output 43200 VA
Maximum AC Power Output 43200 VA
AC Output Line Connections 4-wire WYE (L1-L2-L3-N) plus PE or 3 wire Delta
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-N) 105-120-132.5 Vac
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-L) 183-208-229 Vac
AC Frequency Min-Nom-Max
(1)
59.3 - 60 - 60.5 Hz
Maximum Continuous Output Current (per Phase) @208V 120 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection, Congurable Power Factor,
Country Congurable Thresholds
Ye s
INPUT
Maximum DC Power (Module STC), Inverter / Unit 58200 / 19400 W
Transformer-less, Ungrounded Ye s
Maximum Input Voltage DC to Gnd 300 Vdc
Maximum Input Voltage DC+ to DC- 600 Vdc
Nominal Input Voltage DC to Gnd 200 Vdc
Nominal Input Voltage DC+ to DC- 400 Vdc
Maximum Input Current 114 Adc
Maximum Input Short Circuit Current 135 Adc
Reverse-Polarity Protection Ye s
Ground-Fault Isolation Detection 350kΩ Sensitivity per Unit
CEC Weighted Eciency 97 %
Nighttime Power Consumption < 12 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Cellular GSM (optional)
Rapid Shutdown NEC2014 and NEC2017 compliant/certied, upon AC Grid Disconnect
RS485 Surge Protection Built-in
DC SAFETY SWITCH
DC Disconnect 1000V / 3 x 40A
DC Surge Protection Optional, Type II, eld replaceable
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, CSA 22.2
Grid Connection Standards IEEE 1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class A
INSTALLATION SPECIFICATIONS
Number of units 3
AC Output Conduit Size / Max AWG / Max PE AWG 2” / 4/0 / 4
DC Output Conduit Size / Terminal Block AWG Range /
Number of Strings
(2)
2 x 1.25” / 6-14 / 9 strings
Dimensions (H x W x D)
Primary Unit: 37 x 12.5 x 10.5 / 940 x 315 x 260;
Secondary Unit: 21 x 12.5 x 10.5 / 540 x 315 x 260
in / mm
Weight Primary Unit: 105.8 / 48; Secondary Unit 99.2 / 45 lb / kg
Operating Temperature Range -40 to +140 / -40 to +60
(3)
F / ˚C
Cooling Fan (user replaceable)
Noise < 60 dBA
Protection Rating NEMA 3R
Bracket Mounted (Brackets Provided)
(1)
For other regional settings please contact SolarEdge support
(2)
Single input option per unit (up to 3AWG) available
(3)
For power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf
Three Phase Inverter with Synergy
Technology for the 208V Grid for North America
SE43.2KUS
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All
other trademarks mentioned herein are trademarks of their respective owners. Date: 01/2019/V01/ENG NA. Subject to change without notice.