Installation Guide
To connect the RS485 communication bus:
1.
Open the communication gland.
CAUTION!
The gland includes a rubber waterproof fitting, which should be used to
ensure proper sealing.
ATTENTION!
Le cote interne du gland contient une rondelle qui doit être utilisée pour
une bonne étancheïté.
2.
Remove the rubber fitting from the gland and insert the CAT5/6 cable through the
gland and through the gland opening in the Connection Unit.
Figure 39: Inserting communication cables
3. Remove the seal from one of the openings in the communication glandand insert
the wire through the opening.
4.
Pull out both 3 -pin RS485 terminal blocks, as shown below:
Figure 40: RS485 connectors and termination switch
Three Phase Inverter with Synergy Technology Installation MAN-01-00401-1.5
78 Creating an RS485 Bus Connection