Installation Guide
2. Remove the dummy fuse from the 3-wire grid fuse holder and set it aside.
3. Move the fuse from the 4-wire grid fuse holder to the 3-wire grid fuse holder.
4. Place the dummy fuse in the 4-wire grid fuse holder.
5. During system setup, set the country to the appropriate 3-wire grid option. Using
the non-3-wire setting may result in incorrect system operation.
CAUTION!
If the fuse was moved to support one of the grid types, do not connect the
inverter to the other grid type without switching the fuse back to the correct
holder. Connecting the inverter to grids when the fuse is incorrectly located
may damage the inverter and void the warranty.
ATTENTION!
Si le fusible a été déplacé pour supporter l’un des types de réseau, ne branchez
pas l’onduleur sur l’autre type de réseau avant de remettre le fusible dans son
bon support. Brancher l’onduleur au réseau quand le fusible est mal placé, peut
endommager l’onduleur et annuler la garantie.
Three Phase Inverter with Synergy Technology Installation MAN-01-00401-1.5
50 Setting the Inverter to Support 208V 3-wire Grid