Cut Sheet
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE
are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein
are trademarks of their respective owners. Date: 07/2018/V01/ENG NAM. Subject to change without notice.
SE43.2KUS
OUTPUT
RatedACPowerOutput 43200 VA
MaximumACPowerOutput 43200 VA
ACOutputLineConnecons 4-wireWYE(L1-L2-L3-N)plusPEor3wireDelta
ACOutputVoltageMinimum-Nominal-Maximum
(1)
(L-N) 105-120-132.5 Vac
ACOutputVoltageMinimum-Nominal-Maximum
(1)
(L-L) 183-208-229 Vac
ACFrequencyMin-Nom-Max
(1)
59.3-60-60.5 Hz
MaximumConnuousOutputCurrent(perPhase)@208V 120 A
GFDIThreshold 1 A
UlityMonitoring,IslandingProtecon,CongurablePower
Factor,CountryCongurableThresholds
Yes
INPUT
MaximumDCPower(ModuleSTC),Inverter/Unit 58200/19400 W
Transformer-less,Ungrounded Yes
MaximumInputVoltageDCtoGnd 300 Vdc
MaximumInputVoltageDC+toDC- 600 Vdc
NominalInputVoltageDCtoGnd 200 Vdc
NominalInputVoltageDC+toDC- 400 Vdc
MaximumInputCurrent 114 Adc
MaximumInputShortCircuitCurrent 135 Adc
Reverse-PolarityProtecon Yes
Ground-FaultIsolaonDetecon 350kΩSensivityperUnit
CECWeightedEciency 97 %
NighmePowerConsumpon <12 W
ADDITIONAL FEATURES
SupportedCommunicaonInterfaces RS485,Ethernet,CellularGSM(oponal)
RapidShutdown NEC2014andNEC2017compliant/cered,uponACGridDisconnect
RS485SurgeProtecon Built-in
DC SAFETY SWITCH
DCDisconnect 1000V/3x40A
DCSurgeProtecon Oponal,TypeII,eldreplaceable
DCFusesonPlus&Minus Oponal,25A
STANDARD COMPLIANCE
(2)
Safety UL1741,UL1741SA,UL1699B,UL1998,CSA2.22
GridConneconStandards IEEE1547,Rule21,Rule14(HI)
Emissions FCCpart15classA
INSTALLATION SPECIFICATIONS
Numberofunits 3
ACOutputConduitSize/MaxAWG/MaxPEAWG 2”/4/0/4
DCOutputConduitSize/TerminalBlockAWGRange/
NumberofStrings
(3)
2x1.25”/6-14/9strings
Dimensions(HxWxD)
PrimaryUnit:37x12.5x10.5/940x315x260;
SecondaryUnit:21x12.5x10.5/540x315x260
in/mm
Weight PrimaryUnit:105.8/48;SecondaryUnit99.2/45 lb/kg
OperangTemperatureRange -40to+140/-40to+60
(4)
F/˚C
Cooling Fan(userreplaceable)
Noise <60 dBA
ProteconRang NEMA3R
BracketMounted(BracketsProvided)
(1)
ForotherregionalsengspleasecontactSolarEdgesupport
(2)
Pending
(3)
Singleinputoponperunit(upto3AWG)available
(4)
Forpowerde-ranginformaonreferto:hps://www.solaredge.com/sites/default/les/se-temperature-derang-note-na.pdf
Three Phase Inverter with Synergy Technology
for the 208V Grid for North America SE43.2KUS