MODEL NUMBER SE14.4KUS SE17.3KUS
APPLICABLE TO INVERTERS WITH PART NUMBER SEXXK
-
USX2IXXXX
OUTPUT
Rated AC Power Output 14400 17300 W
Maximum apparent AC output power 14400 17300 VA
AC Output Line Connections 3W + PE, 4W + PE
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-N) 105-120-132.5 Vac
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-L) 183-208-229 Vac
AC Frequency Min-Nom-Max
(2)
59.3 - 60 - 60.5 Hz
Continuous Output Current (per Phase) 40 48.25 Aac
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection, Country Congurable Set
Points
Yes
THD ≤ 3 %
Power Factor Range +/- 0.85 to 1
INPUT
Maximum DC Power (Module STC) 21600 26000 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage DC+ to DC- 600 Vdc
Nominal Input Voltage DC+ to DC- 400 Vdc
Maximum Input Current 40 48.25 Adc
Maximum Input Short Circuit Current 55 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 167kΩ Sensitivity
(3)
CEC Weighted Efciency 97.5 %
Night-time Power Consumption < 4 W
ADDITIONAL FEATURES
Supported Communication Interfaces 2 x RS485, Ethernet, Cellular (optional)
Inverter Commissioning With the SetApp mobile application using built-in Wi-Fi access point for local connection
Rapid Shutdown NEC2014, NEC2017 and NEC2020 compliant/certied
RS485 Surge Protection Plug-in Supplied with the inverter, Built-in
AC, DC Surge Protection Type II, eld replaceable, Built-in
DC Fuses (Single Pole) 25A, Built-in
Smart Energy Management Export Limitation
DC SAFETY SWITCH
DC Disconnect Integrated
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class A
INSTALLATION SPECIFICATIONS
AC output conduit size /AWG range ¾” or 1” / 6 - 10 AWG
DC input conduit size / AWG range ¾” or 1” / 6 - 12 AWG
Number of DC inputs pairs 4
Dimensions with Safety Switch (H x W x D) 31.8 x 12.5 x 11.8 / 808 x 317 x 300 in / mm
Weight with Safety Switch 78.2 / 35.5 lb / kg
Cooling Fans (user replaceable)
Noise < 62 dBA
Operating Temperature Range -40 to +140 / -40 to +60
(4)
˚F / ˚C
Protection Rating NEMA 3R
Mounting Bracket provided
SE14.4KUS / SE17.3KUS
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are
trademarks of their respective owners. Date: 09/2020/V01/ENG NAM. Subject to change without notice.