Datasheet

Three Phase Inverters for the 277/480V Grid
(1)
For North America
SE30KUS / SE40KUS
MODEL NUMBER
SE30KUS
SE40KUS
UNITS
APPLICABLE TO INVERTERS WITH PART NUMBER
SEXXK-USX8IXXXX
Rated AC Power Output
30000
40000
W
Maximum apparent AC output power
30000
40000
VA
AC Output Line Connections
3W + PE, 4W + PE
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-N)
244 - 277 - 305
Vac
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-L)
422.5 - 480 - 529
Vac
AC Frequency Min-Nom-Max
(2)
59.3 - 60 - 60.5
Hz
Maximum Continuous Output Current (per Phase)
36.25
48.25
Aac
GFDI Threshold
1
A
Utility Monitoring, Islanding Protection, Country Configurable Set Points
Yes
Total Harmonic Distortion
≤ 3
%
Power Factor Range
+/- 0.85 to 1
Maximum DC Power (Module STC)
45000
60000
W
Transformer-less, Ungrounded
Yes
Maximum Input Voltage DC+ to DC-
1000
Vdc
Operating Voltage Range
840 - 1000
Vdc
Maximum Input Current
36.25
48.25
Adc
Maximum Input Short Circuit Current
55
Adc
Reverse-Polarity Protection
Yes
Ground-Fault Isolation Detection
167kΩ Sensitivity
(3)
CEC Weighted Efficiency
98.5
%
Night-time Power Consumption
<4
W
Supported Communication Interfaces
2 x RS485, Ethernet, Cellular (optional)
Inverter Commissioning
With the SetApp mobile application using built-in access point for local connection
Arc Fault Protection
Integrated, User Configurable (According to UL1699B)
Rapid Shutdown
NEC2014, NEC2017 and NEC2020 compliant/certified
RS485 Surge Protection Plug-in
Supplied with the inverter, Built-in
DC Surge Protection
Type II, field replaceable, Built-in
AC Surge Protection
Type II, field replaceable, Built-in
DC Fuses (Single Pole)
25A, Built-in
Smart Energy Management
Export Limitation
DC Disconnect
Integrated
Safety
UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards
IEEE1547, Rule 21, Rule 14 (HI)
Emissions
FCC Part 15 class A
AC output conduit size / AWG range
¾” or 1” / 6 - 10 AWG
DC input conduit size / AWG range
¾” or 1” / 6 - 12 AWG
Number of DC inputs pairs
4
Dimensions with Safety Switch (H x W x D)
31.8 x 12.5 x 11.8 / 808 x 317 x 300
in / mm
Weight with Safety Switch
78.2 / 35.5
lb / kg
Cooling
Fans (user replaceable)
Noise
< 62
dBA
Operating Temperature Range
-40 to +140 / -40 to +60
(4)
˚F / ˚C
Protection Rating
NEMA 3R
Mounting
Bracket provided
(1) For 120/208V inverters refer to: https://www.solaredge.com/sites/default/files/se-three-phase-us-inverter-208V-setapp-datasheet.pdf.
(2) For other regional settings please contact SolarEdge support.
(3) Where permitted by local regulations.
(4) For power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf.
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: May 11, 2022 DS-000070-NA. Subject to change without notice.