Install Manual

Table Of Contents
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US UNITS
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, UL9540, CSA 22.2
Grid Connection Standards IEEE1547, Rule 21, Rule 14H
Emissions FCC part15 class B
INSTALLATION SPECIFICATIONS
AC Output Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
EV AC Output Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
DC Input (PV) Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
DC Input (Battery) Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
Dimensions with Connection Unit (HxWxD) 17.7 X 14.6 X 6.8 / 450 X 370 X 174
in /
mm
Weight with Connection Unit 26 / 11.8 29.1 / 3.2 30.2 / 13.7
lb /
kg
Noise < 25 dBA
Cooling Natural Convection
Operating Temperature Range -40 to +140 / -40 to +60
(1)
˚F / ˚C
Protection Rating NEMA 4X
(1)
Full power up to at least 50°C / 122°F; for power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-
derating-note-na.pdf
SolarEdge-Single Phase Energy Hub Inverter with Prism Technology MAN-01-00671-1.2