Connecting the Battery (Optional)
WARNING!
The storage system battery must be powered off before and during wiring.
To power off the battery:
1. Turn off the circuit breaker.
2. Turn off the disconnect/auxiliary power switch.
To power the battery back on:
1. Turn on the disconnect/auxiliary power switch.
2. Turn on the circuit breaker.
For details, see
Powering the LG Chem Battery Off and On
on page 71.
AVERTISSEMENT!
La batterie doit être éteinte avant et durant le câblage:
Pour éteindre la batterie:
1.
Fermez le disjoncteur.
2. Fermez l’interrupteur auxiliaire.
Pour rallumer la batterie:
1.
Ouvrez l’interrupteur auxiliaire.
2. Ouvrez le disjoncteur.
Pour plus details, consultez Powering the LG Chem Battery Off and On page
71.
When connecting the battery to the inverter, use the following cable types:
DC - a pair of PV DC cables, DC cable 10 AWG (10-14 AWG), 600V insulated
Communication - 24 AWG (16-24AWG), 600V insulated or CAT5
To connect the battery:
1. Connect the DCand communication cables to the battery, as explained in the
manual that comes with the battery.
2. Pass the other end of the communication cable through Communication gland 2.
3. Remove the 8-pin connector from the port labeled Other Inverter-Battery on the
communication board.
Chapter 5: Connecting the Inverter 39