NOTE
Functional electrical earthing of DC-side negative or positive poles is prohibited
because the inverter has no transformer. Grounding (earth ground) of panel
frames and mounting equipment of the PV array panels is acceptable.
NOTE
SolarEdge’s fixed input voltage architecture enables the parallel strings to be of
different lengths. Therefore, they do not need to have the same number of
power optimizers, as long as the length of each string is within the permitted
range.
To connect to DCstrings:
1.
Strip 5.16''/8 mm of the DC wires insulation.
2. Pass the DCwires through the conduit.
3.
Connect the wires to the DCterminals as shown below. Observe the correct polarity
as labeled on the terminals.
Figure 18: Inverter DC Connections
Single Phase Energy Hub Inverter with Prism Technology MAN-01-00671-1.2
38 Connecting the DC Strings to the Inverter