Energy Hub with Prism Technology Specifications

SMART ENERGY CAPABILITIES
Consumption Metering Built-in
(6)
Battery Storage
With Backup Interface for service up to 200A; Up to 3 inverters, 15kW backup power, and 60kWh backup
capacity
EV Charging Direct connection to Smart EV charger
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Wi-Fi (optional), Cellular
Revenue Grade Metering, ANSI C12.20 Built - in
(6)
Integrated AC, DC and Communication Connection Unit Ye s
Inverter Commissioning with the SetApp mobile application using built-in Wi-Fi Access Point for local connection
DC Voltage Rapid Shutdown (PV and Battery) Yes, according to NEC 2014 and 2017 690.12
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, UL9540, CSA 22.2
Grid Connection Standards IEEE1547, Rule 21, Rule 14H
Emissions FCC part15 class B
INSTALLATION SPECIFICATIONS
AC Output Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
EV AC Output Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
DC Input (PV) Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
DC Input (Battery) Conduit Size / AWG Range 3/4'' maximum / 14-8 AWG 1'' maximum / 14-6 AWG
Dimensions with Connection Unit (HxWxD) 17.7 X 14.6 X 6.8 / 450 X 370 X 174 in / mm
Weight with Connection Unit 26 / 11.8 30.2 / 13.7 lb / kg
Noise < 25 dBA
Cooling Natural Convection
Operating Temperature Range -40 to +140 / -40 to +60
(7)
˚F / ˚C
Protection Rating NEMA 4X
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All
other trademarks mentioned herein are trademarks of their respective owners. Date: 06/2020/V01/ENG NAM. Subject to change without notice.
(1) These specications apply to inverters with part numbers SExxxxH-USS3xxxxx or SE7600H-USSSHxxxx and connection unit model number DCD-1PH-US-PxH-F-x
(2) For other regional settings please contact SolarEdge support
(3) Not designed for standalone applications and requires AC for commissioning
(4) A higher current source may be used; the inverter will limit its input current to the values stated
(5) When connecting two LG Chem RESU batteries, each battery must have a different part number
(6) For consumption metering current transformers should be ordered separately: SEACT0750-200NA-20 or SEACT0750-400NA-20. 20 units per box.
(7) Full power up to at least 50°C / 122°F; for power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf
Connecting CTs to the Revenue Grade and Consumption Meter
Single Phase Energy Hub Inverter
with Prism Technology
Grid
Single Phase Energy Hub Inverter
with Prism Technology
for North America
SE3000H-US / SE3800H-US / SE6000H-US / SE7600H-US
(1)