Energy Hub with Prism Technology Installation Guide

Table Of Contents
Single Phase Energy Hub Inverter with Prism Technology - Technical
Specifications
for North America
SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US / SE7600H-US
(1)
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US UNITS
OUTPUT - AC ON GRID
Rated AC Power 3000 3800 5000 6000 7600 W
Maximum AC Power Output 3000 3800 5000 6000 7600 W
AC Output Voltage Range 211-264 Vac
AC Frequency Range (min - nom - max) 59.3 - 60 - 60.5
(2)
Hz
Maximum Continuous Output Current 12.5 16 21 25 32 A
GFDI Threshold 1 A
Total Harmonic Distortion (THD) <3 %
Power Factor 1, adjustable -0.85 to 0.85
Utility Monitoring, Islanding Protection,
Country Configurable Thresholds
Yes
Charge Battery from AC (if Allowed) Yes
(1)
These specifications apply to inverters with PNs SExxxxH-USS3xxxxx or SE7600H-USSSHxxxx and connection unit PNs DCD-1PH-US-PxH-F-x .
(2)
For other regional settings please contact SolarEdge support.
SolarEdge-Single Phase Energy Hub Inverter with Prism Technology MAN-01-00671-1.3