Datasheet

* Supported with PN SE3800H-USMxxxxxx
(1) These specications apply to inverters with part numbers SExxxxH-USS3Bxxxx, SE3800H-USMxxBCxx or SE7600H-USSSHxxxx and connection unit model number DCD-1PH-US-PxH-F-x
(2) For other regional settings please contact SolarEdge support
(3) Not designed for standalone applications and requires AC for commissioning
(4) Rated AC power in Backup Operation are valid for installations with multiple inverters. For a single backup inverter operation, rated AC power in Backup is 90% of the value stated
(5) A higher current source may be used; the inverter will limit its input current to the values stated
(6) Requires supporting inverter FW for RESU16H Prime battery
(7) When connecting two LG Chem RESU10H batteries, each battery must have a different part number. LG Chem RESU16H Prime is supported with a single battery only
(8) Discharge power is limited up to inverter rated AC power
(9) For consumption metering current transformers should be ordered separately: SEACT0750-200NA-20 or SEACT0750-400NA-20. 20 units per box.
Revenue grade metering is only for production metering
(10) For all cellular plans customer must verify that:
· Customer is responsible for verifying that the site location has adequate mobile coverage by the third party service provider prior to any installation by accessing https://www.solaredge.com/products/
communication/cellular-communication-options#/
· SolarEdge shall not be responsible or liable for unavailability or discontinuance of network coverage in a specic area or region, any network downtime, or permanent service shutdown
(11) Full power up to at least 50°C / 122°F; for power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf
SE3000H-US / SE3800H-US / SE6000H-US / SE7600H-US
(1)
SE3000H-US SE3800H-US SE6000H-US SE7600H-US UNITS
SMART ENERGY CAPABILITIES
Consumption Metering Built - in
(9)
Backup & Battery Storage
With Backup Interface (purchased separately) for service up to 200A; Up to 3 inverters, 15kW backup
power, and 60kWh backup capacity
EV Charging Direct connection to Smart EV charger
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Wi-Fi (optional), Cellular
(10)
Revenue Grade Metering, ANSI C12.20 Built - in
(9)
Integrated AC, DC and Communication Connection Unit Ye s
Inverter Commissioning With the SetApp mobile application using built-in Wi-Fi Access Point for local connection
DC Voltage Rapid Shutdown (PV and Battery) Yes, according to NEC 2014, NEC 2017 and NEC 2020 690.12
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1741 PCS, UL1699B, UL1998, UL9540, CSA 22.2
Grid Connection Standards IEEE1547, Rule 21, Rule 14H
Emissions FCC part 15 class B
INSTALLATION SPECIFICATIONS
AC Output Conduit Size / AWG Range
3/4'' maximum /
14-8 AWG
3/4'' maximum / 14-8 AWG
1'' maximum / 14-4 AWG
1'' maximum / 14-4 AWG*
EV AC Output Conduit Size / AWG Range
3/4'' maximum /
14-8 AWG
3/4'' maximum / 14-8 AWG
1'' maximum / 14-4 AWG
1'' maximum / 14-64AWG*
DC Input (PV) Conduit Size / AWG Range
3/4'' maximum /
14-8 AWG
3/4'' maximum / 14-8 AWG
1'' maximum / 14-6 AWG
1'' maximum / 14-6 AWG*
DC Input (Battery) Conduit Size / AWG Range
3/4'' maximum /
14-8 AWG
3/4'' maximum / 14-8 AWG
1'' maximum / 14-6 AWG
1'' maximum / 14-6 AWG*
Dimensions with Connection Unit (H x W x D) 17.7 x 14.6 x 6.8 / 450 x 370 x 174 in / mm
Weight with Connection Unit 26 / 11.8
26 / 11.8
30.2 / 13.7 lb / kg
30.2 / 13.7
*
Noise < 25
< 25
< 50 dBA
< 50
*
Cooling Natural Convection
Operating Temperature Range -40 to +140 / -40 to +60
(11)
˚F / ˚C
Protection Rating NEMA 4
Single Phase Energy Hub Inverter
with Prism Technology
for North America