INVERTER SPECIFICATIONS:
SE3800H-US SE5000H-US SE6000H-US SE7600H-US
OUTPUT
Rated AC Power Output
3800 @ 240V
3300 @ 208V
5000
6000 @ 240V
5000 @ 208V
7600 VA
Max. AC Power Output
3800 @ 240V
3300 @ 208V
5000
6000 @ 240V
5000 @ 208V
7600 VA
AC Output Voltage Min.-Nom.-Max. (183 - 208 - 229) 3 - 3 - Vac
AC Output Voltage Min.-Nom.-Max. (211 - 240 - 264) 3 3 3 3 Vac
AC Frequency (Nominal) 59.3 - 60 - 60.5
(1)
Hz
Maximum Connuous Output Current 208V 16 - 24 - A
Maximum Connuous Output Current @240V 16 21 25 32 A
GFDI Threshold 1 A
Ulity Monitoring, Islanding Protecon, Country
C o n gu rab le Th re s h o l d s
Yes
INPUT
Maximum DC Power @240V 5900 7750 9300 11800 W
Maximum DC Power @208V 5100 - 7750 -
Transformer-less, Ungrounded Yes
Maximum Input Voltage 480 Vdc
Nominal DC Input Voltage 380
400
Vdc
Maximum Input Current 208V 9 - 13.5 -
Maximum Input Current @240V 10.5 13.5 16.5 20 Adc
Max. Input Short Circuit Current 45 Adc
Reverse-Polarity Protecon Yes
Ground-Fault Isolaon Detecon 600k Sensivity
Maximum Inverter Eciency 99.2 %
CEC Weighted Eciency 99 %
Nighme Power Consumpon < 2.5 W
ADDITIONALFEATURES
Supported Communicaon Interfaces RS485, Ethernet, ZigBee (oponal), Cellular (oponal)
Revenue Grade Data, ANSI C12.20 Oponal
(2)
Rapid Shutdown - NEC 2014 and 2017 690.12 Automac Rapid Shutdown upon AC Grid Disconnect
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connecon Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC Part 15 Class B
INSTALLATION SPECIFICATIONS
AC Output Conduit Size / AWG Range 3/4” minimum / 20-4 AWG
DC Input Conduit Size / # of Strings / AWG Range 3/4” minimum / 1-2 strings / 14-6 AWG
Dimensions with Safety Switch (HxWxD) 17.7 x 14.6 x 6.8 / 450 x 370 x 174 in / mm
Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 lb / kg
Noise < 25 <50 dBA
Cooling Natural Convecon
Operang Temperature Range -13 to +140 / -25 to +60
(3)
(-40˚F / -40˚C opon)
(4)
˚F / ˚C
Protecon Rang NEMA 3R (Inverter with Safety Switch)
(1)
For other regional sengs please contact SolarEdge support
(2)
Revenue grade inverter P/N: SExxxxH-US000NNC2
OUTPUT—AC
Charging Level
AC Level 2
Connecon to the SolarEdge monitoring plaorm is required for rst EV charging
Rated AC Power Output (grid & PV) 9600 W
Nominal AC Output Voltage 240 Vac
Nominal AC Frequency 60 Hz
Maximum Connuous Output Current @240V (grid & PV) 40 Aac
Ground Fault Detecon Threshold 5 mA
ADDITIONALFEATURES
EV Charger Status LEDs, Fault Indicator Yes
EV Charger Unplugging Detecon Yes, current terminaon according to SAE J1772
EV Charger Ground Connecon Monitoring Yes, connuous
EV Charger Conguraon Via the monitoring app; Ethernet or ZigBee connecon is required
(5)
STANDARD COMPLIANCE
Safety
(6)
UL2594, UL2231-1, UL2231-2, NEC Arcle 625 compliant
EV Charger SAE J1772-2009
INSTALLATION SPECIFICATIONS
EV Charger Connector SAE J1772-2009
EV Charger Cable Length
(7)
25 / 7.6 (15 / 4.6 opon) / m
EV Charger Cable Weight 12.5 / 5.7 (7.7 / 3.5 for 15 / 4.6m opon) lb / kg
EV Charger Cable Operang Temperature Range -22 to 122 / -30 to +50 ˚F / ˚C
Protecon Rang (connected to EV or with dust cap) NEMA 3R
EV CHARGER AND EV CHARGER CABLE SPECIFICATIONS:
(5)
Cellular connecon may be used; requires a SIM card with a 1GB data plan that should be purchased from a cellular provider
(6)
Pending cercaon
(7)
EV charger cable ordered separately
(3)
For power de-rang informaon refer to: hps://www.solaredge.com/sites/default/les/se-temperature-derang-note-na.pdf
(4)
-40 version P/N: SExxxxH-US000NNU4