Product Specifications
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: 12/2018/V01/ENG NAM. Subject to change without notice.
Three Phase Inverters
For the 277/480V Grid
(1)
for North America
SE10KUS / SE20KUS / SE30KUS / SE33.3KUS
SE10KUS SE20KUS SE30KUS SE33.3KUS
OUTPUT
Rated AC Power Output 10000 20000 30000 33300 VA
Maximum AC Power Output 10000 20000 30000 33300 VA
AC Output Line Connections 4-wire WYE (L1-L2-L3-N) plus PE
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-N) 244-277-305 Vac
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-L) 422.5-480-529 Vac
AC Frequency Min-Nom-Max
(2)
59.3 - 60 - 60.5 Hz
Max. Continuous Output Current (per Phase) 12 24 36.5 40 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection,
Countr y Congurable Set Points
Ye s
INPUT
Maximum DC Power (Module STC) 13500 27000 40500 45000 W
Transformer-less, Ungrounded Ye s
Maximum Input Voltage DC to Gnd 490 Vdc
Maximum Input Voltage DC+ to DC- 980 Vd c
Nominal Input Voltage DC to Gnd 420 Vdc
Nominal Input Voltage DC+ to DC- 840 Vdc
Maximum Input Current 13.5 26.5 39 40 Adc
Maximum Input Short Circuit Current 45 Adc
Reverse-Polarity Protection Ye s
Ground-Fault Isolation Detection 1MΩ Sensitivity 350kΩ Sensitivity
(3)
CEC Weighted Eciency 98 98.5 %
Night-time Power Consumption < 3 < 4 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, ZigBee (optional)
Rapid Shutdown – NEC 2014 and 2017 690.12 Automatic Rapid Shutdown upon AC Grid Disconnect
RS485 Surge Protection Supplied with the inverter
STANDARD COMPLIANCE
Safety
UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to
T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class B
INSTALLATION SPECIFICATIONS
AC output conduit size / AWG range 3/4” minimum / 12-6 AWG 3/4” minimum / 8-4 AWG
DC input conduit size / AWG range 3/4” minimum / 12-6 AWG
Number of DC inputs 2 pairs 3 pairs
(4)
Dimensions (H x W x D) 21 x 12.5 x 10.5 / 540 x 315 x 260 in / mm
Dimensions with Safety Switch (H x W x D) 30.5 x 12.5 x 10.5 / 775 x 315 x 260 in / mm
Weight 73.2 / 33.2 99.5 / 45 lb / kg
Weight with Safety Switch 79.7 / 36.2 106 / 48 lb / kg
Cooling Fans (user replaceable)
Noise < 50 < 55 dBA
Operating Temperature Range -40 to +140 / -40 to +60
(5)
˚F / ˚C
Protection Rating NEMA 3R
(1)
For 208V inverters refer to: http://www.solaredge.com/les/pdfs/products/inverters/se-three-phase-us-inverter-208V-datasheet.pdf
(2)
For other regional settings please contact SolarEdge support
(3)
Where permitted by local regulations
(4)
Field replacement kit for 1 pair of inputs P/N: DCD-3PH-1TBK; Field replacement kit for 3 pairs of fuses and holders P/N: DCD-3PH-6FHK-S1
(5)
For power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf