Energy Hub with Prism Technology Installation Guide

Table Of Contents
Connecting the Battery (Optional)
WARNING!
The storage system battery must be powered off before and during wiring.
To power off the battery:
1. Turn off the circuit breaker.
2. Turn off the disconnect/auxiliary power switch.
To power the battery back on:
1. Turn on the disconnect/auxiliary power switch.
2. Turn on the circuit breaker.
For details, see
Powering the LG Chem Battery Off and On
on page 71.
AVERTISSEMENT!
La batterie doit être éteinte avant et durant le câblage:
Pour éteindre la batterie:
1.
Fermez le disjoncteur.
2. Fermez l’interrupteur auxiliaire.
Pour rallumer la batterie:
1.
Ouvrez l’interrupteur auxiliaire.
2. Ouvrez le disjoncteur.
Pour plus details, consultez Powering the LG Chem Battery Off and On page
71.
When connecting the battery to the inverter, use the following cable types:
DC - a pair of PV DC cables, DC cable 10 AWG (10-14 AWG), 600V insulated
Communication - 24 AWG (16-24AWG), 600V insulated or CAT5
To connect the battery:
1. Connect the DCand communication cables to the battery, as explained in the
manual that comes with the battery.
2. Pass the other end of the communication cable through Communication gland 2.
3. Remove the 8-pin connector from the port labeled 2nd Inv-Battery on the
communication board.
Chapter 5: Connecting the Inverter 39
Single Phase Energy Hub Inverter with Prism Technology MAN-01-00671-1.3