MODEL NUMBER SE20KUS SE30KUS SE33.3KUS SE40KUS
APPLICABLE TO INVERTERS WITH PART NUMBER
SEXXK
-
USXXXBXXX
SEXXK
-
USX8IXXXX
OUTPUT
Rated AC Power Output 20000 30000 33300 40000 W
Maximum apparent AC output power 20000 30000 33300 40000 VA
AC Output Line Connections 4W + PE 3W + PE, 4W + PE
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-N) 244 - 277 - 305 Vac
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-L) 422.5 - 480 - 529 Vac
AC Frequency Min-Nom-Max
(2)
59.3 - 60 - 60.5 Hz
Maximum Continuous Output Current (per Phase) 24 36.25 40 48.25 Aac
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection, Country Congurable Set Points Yes
Total Harmonic Distortion ≤ 3 %
Power Factor Range +/- 0.85 to 1
INPUT
Maximum DC Power (Module STC) 27000 45000 50000 60000 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage DC+ to DC- 1000 Vdc
Nominal Input Voltage DC+ to DC- 850 Vdc
Maximum Input Current 26.5 36.25 40 48.25 Adc
Maximum Input Short Circuit Current 33 55 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 1MΩ Sensitivity 167kΩ Sensitivity
(3)
CEC Weighted Efciency 98 98.5 %
Night-time Power Consumption <3 <4 W
ADDITIONAL FEATURES
Supported Communication Interfaces 2 x RS485, Ethernet, Cellular (optional)
Inverter Commissioning With the SetApp mobile application using built-in access point for local connection
Arc Fault Protection Integrated, User Congurable (According to UL1699B)
Rapid Shutdown NEC2014, NEC2017 and NEC2020 compliant/certied
RS485 Surge Protection Plug-in Supplied with the inverter, Built-in
DC Surge Protection
Type II, eld
replaceable, optional
Type II, eld replaceable, Built-in
AC Surge Protection - Type II, eld replaceable, Built-in
DC Fuses (Single Pole) - 25A, Built-in
Smart Energy Management Export Limitation
DC SAFETY SWITCH
DC Disconnect Integrated
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class A
INSTALLATION SPECIFICATIONS
AC output conduit size / AWG range
3/4” minimum /
12-6 AWG
¾” or 1” / 6 - 10 AWG
DC input conduit size / AWG range ¾” or 1” / 6 - 12 AWG
Number of DC inputs pairs 2 4
Dimensions with Safety Switch (H x W x D)
30.5 x 12.5 x 10.5 /
775 x 315 x 260
31.8 x 12.5 x 11.8 / 808 x 317 x 300 in / mm
Weight with Safety Switch 74.2 / 33.7 78.2 / 35.5 lb / kg
Cooling Fans (user replaceable)
Noise < 50 < 62 dBA
Operating Temperature Range -40 to +140 / -40 to +60
(4)
˚F / ˚C
Protection Rating NEMA 3R
Mounting Bracket provided