SE20KUS - SE33.3KUS Inverters with SetApp configuration for the 277/480V Grid
Three Phase Inverters for the 277/480V Grid
(1)
for North America
(1) For 120/208V inverters refer to: https://www.solaredge.com/sites/default/les/se-three-phase-us-inverter-208V-setapp-datasheet.pdf
(2) For other regional settings please contact SolarEdge support
(3) Where permitted by local regulations
(4) Field replacement kit for 1 pair of inputs P/N: DCD-3PH-1TBK; Field replacement kit for 3 pairs of fuses and holders P/N: DCD-3PH-6FHK-S1
(5) For power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf
MODEL NUMBER SE20KUS SE30KUS SE33.3KUS
APPLICABLE TO INVERTERS
WITH PART NUMBER
SEXXK
-
XXXXXBXX4
OUTPUT
Rated AC Power Output 20000 30000 33300 VA
Maximum AC Power Output 20000 30000 33300 VA
Output Line Connections 3 phase, 4-wire / PE (L1-L2-L3-N), TN, TT
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-N) 244-277-305 Vac
AC Output Voltage Minimum-Nominal-Maximum
(2)
(L-L) 422.5-480-529 Vac
AC Frequency Min-Nom-Max
(2)
59.3 - 60 - 60.5 Hz
Maximum Continuous Output Current (per Phase) 24 36.5 40 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection, Country Congurable Set Points Yes
THD ≤ 3 %
INPUT
Maximum DC Power (Module STC) 27000 40500 45000 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage DC to Gnd 490 Vdc
Maximum Input Voltage DC+ to DC- 1000 Vdc
Nominal Input Voltage DC to Gnd 420 Vdc
Nominal Input Voltage DC+ to DC- 850 Vdc
Maximum Input Current 26.5 39 40 Adc
Maximum Input Short Circuit Current 45 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 1MΩ Sensitivity 350kΩ Sensitivity
(3)
CEC Weighted Eciency 98 98.5 %
Night-time Power Consumption < 3 < 4 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Built-in Cellular (optional)
Inverter Commissioning With the SetApp mobile application using built-in access point for local connection
Rapid Shutdown – NEC 2014 and 2017 690.12 Automatic Rapid Shutdown upon AC Grid Disconnect
(4)
RS485 Surge Protection Plug-in Supplied with the inverter
Smart Energy Management Export Limitation
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class B
INSTALLATION SPECIFICATIONS
AC output conduit size / AWG range
3/4” minimum / 12-6
AWG
3/4” minimum / 8-4 AWG
DC input conduit size / AWG range 3/4” minimum / 12-6 AWG
Number of DC inputs 2 pairs 3 pairs
(4)
Dimensions (H x W x D) 21 x 12.5 x 10.5 / 540 x 315 x 260 in / mm
Dimensions with Safety Switch (H x W x D) 30.5 x 12.5 x 10.5 / 775 x 315 x 260 in / mm
Weight 73.2 / 33.2 93.6 / 42.5 lb / kg
Weight with Safety Switch 79.7 / 36.2 100.3 / 45.5 lb / kg
Cooling Fans (user replaceable)
Noise < 50 < 55 dBA
Operating Temperature Range -40 to +140 / -40 to +60
(5)
˚F / ˚C
Protection Rating NEMA 3R
SE20KUS / SE30KUS / SE33.3KUS
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or regiered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein
are trademarks of their respective owners. Date: 07/2020/V01/ENG NAM. Subject to change without notice.