Problem Possible Cause Possible Solution
String voltage is higher than
the number of optimizers
WARNING!
If the measured voltage is
too high, the installation may
not have a safe low voltage.
PROCEED WITH CARE! A
deviation of ±1% per string is
reasonable.
Si la tension mesuree est
trop haute, la tension basse
de securite pourrait
manquer dans l’installation.
REDOUBLEZ DE
PRECAUTION. Une
deviation de ±1% par string
est raisonnable.
One or more extra power optimizer
are connected in the string
Check if an extra power
optimizer is connected in the
string. If not proceed to next
solution.
A module is connected directly to the
string, without a power optimizer.
Verify that only power
optimizers are connected in the
string and that no module
outputs are connected without
a power optimizer. If the
problem persists, proceed to
the next step.
A malfunction of one of the power
optimizers
o
Disconnect the wires that
connect the power
optimizers in the string.
o
Measure the output voltage
of each power optimizer in
order to locate the power
optimizer that does not
output the 1V safety
voltage.If a malfunctioning
power optimizer is located,
check its connections,
polarity, module, and
voltage.
o
Do not continue before
finding the problem and
replacing the malfunctioning
power optimizer.If a
malfunction cannot be
bypassed or resolved, skip
the malfunctioning power
optimizer, thus connecting
a shorter string.
Appendix A: Errors and Troubleshooting
SolarEdge-Installation Guide MAN-01-00002-4.0