Install Manual
Table Of Contents
- Disclaimers
- Revision History
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizer
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Activating, Commissioning and Configuring the System
- Chapter 6: Setting Up Communication to the Monitoring Platform
- Appendix A: Errors and Troubleshooting
- Appendix B: Mechanical Specifications
- Appendix C: External Fan Maintenance and Replacement
- Appendix D: Replacing and Adding System Components
- Determining the Circuit Breaker Size
- Support Contact Information
Technical Specifications - Three Phase Inverters (North America)
SE9KUS SE10KUS SE14.4KUS SE20KUS SE30KUS SE33.3KUS Units
Supported grid 120 / 208 277 / 480 120 / 208 277 / 480
OUTPUT
Rated AC power output 9000 10000 14400 20000 30000 33300 VA
Maximum AC power output 9000 10000 14400 20000 30000 33300 VA
AC Output Line Connections
3 Phase, 3-
wire / PE (L1-
L2-L3), TN, TT
3 phase, 4-
wire / PE (L1-
L2-L3-N), TN,
TT
3 phase, 4-
wire / PE (L1-
L2-L3-N), TN,
TT
3 Phase, 3-
wire / PE (L1-
L2-L3), TN, TT
3 phase, 4-
wire / PE (L1-
L2-L3-N), TN,
TT
3 phase, 4-wire / PE (L1-L2-L3-N), TN, TT
AC output voltage minimum-
nominal-maximum (L-N)
(1)
105-120-
132.5
244-277-305
105-120-
132.5
244-277-305 244-277-305 244-277-305 Vac
AC output voltage minimum-
nominal-maximum (L-L)
1
183-208-229
422.5-480-
529
183-208-229
422.5-480-
529
422.5-480-
529
422.5-480-
529
Vac
AC frequency min-nom-max
1
59.3 - 60 - 60.5
(with HI country setting 57 - 60 - 60.5)
Hz
(1)
For other regional settings please contact SolarEdge Support.
Three
Phase
Inverter
Specifications
(North America
)
MAN-01-00529
-1.3
1