Install Manual

Table Of Contents
1. Insert the screwdriver into the front opening and rotate it counterclockwise to
activate the clamp mechanism. The side latch holds the clamp in the open
position.
2. Insert the wire into the side opening as deep as possible.
3. Slightly rotate the screwdriver counter-clockwise to release the latch.
4. Remove the screwdriver – the wire is safely clamped.
Figure 22: AC Spring-clamp terminal example - 33.3KW inverter
6. Verify that there are no unconnected wires.
To connect the AC grid to the Safety Switch – 9kW, 10kW, 20kW:
1. Strip 0516'' (8mm) of the AC wire insulation.
2.
Insert the AC conduit into the AC-side drill guide that was opened.
NOTE
Connect the equipment grounding before connecting the AC wires to the
AC.
Veillez à relier le conducteur de PE (la terre) avant de connecter les fils CA
au bornier CA.
Chapter 4: Connecting the AC and the Strings to the Safety Switch 43
Three Phase System Installation Guide MAN-01-00527-1.4